Stuck in a stack—Temperature measurements of the microclimate around split type condensing units in a high rise building in Singapore

Journal article


Bruelisauer, M, Meggers, F, Mahmoudi Saber, E., Li, C and Leibundgut, H (2013). Stuck in a stack—Temperature measurements of the microclimate around split type condensing units in a high rise building in Singapore. Energy and Buildings. 71, pp. 28-37.
AuthorsBruelisauer, M, Meggers, F, Mahmoudi Saber, E., Li, C and Leibundgut, H
Abstract

The use of air-conditioning, the largest energy demand for buildings in the tropics, is increasing as regional population and affluence grow. The majority of installed systems are split type air-conditioners. While the performance of new equipment is much better, the influence of the microclimate where the condensing units are installed is often overlooked. Several studies have used CFD simulations to analyse the stack effect, a buoyancy-driven airflow induced by heat rejected from condensing units. This leads to higher on-coil temperatures, deteriorating the performance of the air-conditioners. We present the first field measurements from a 24-storey building in Singapore. A network of wireless temperature sensors measured the temperature around the stack of condensing units. We found that the temperatures in the void space increased continuously along the height of the building by 10–13 °C, showing a significant stack effect from the rejected heat from condensing units. We also found that hot air gets stuck behind louvres, built as aesthetic barriers, which increases the temperature another 9 °C. Temperatures of around 50 °C at the inlet of the condensing units for floors 10 and above are the combined result, reducing the unit efficiency by 32% compared to the undisturbed design case. This significant effect is completely neglected in building design and performance evaluation, and only with an integrated design process can truly efficient solutions be realised.

Keywords09 Engineering; 12 Built Environment And Design; Building & Construction
Year2013
JournalEnergy and Buildings
Journal citation71, pp. 28-37
PublisherLondon South Bank University
ISSN0378-7788
Digital Object Identifier (DOI)doi:10.1016/j.enbuild.2013.11.056
Publication dates
Print23 Nov 2013
Publication process dates
Deposited06 Dec 2017
Accepted12 Nov 2013
Accepted author manuscript
License
CC BY-NC-ND 4.0
File Access Level
Open
Permalink -

https://openresearch.lsbu.ac.uk/item/878v3

  • 1
    total views
  • 31
    total downloads
  • 1
    views this month
  • 4
    downloads this month

Related outputs

Limits and uncertainty for energy efficiency in the UK housing stock
Gillich, A., Mahmoudi Saber, E. and Mohareb, E. (2019). Limits and uncertainty for energy efficiency in the UK housing stock. Energy Policy. 133.
Performance evaluation of damper control settings for operation of multiple-zone variable air volume reheat system in different building applications and climate types
Mahmoudi Saber, E. (2017). Performance evaluation of damper control settings for operation of multiple-zone variable air volume reheat system in different building applications and climate types. Building Simulation. 10 (5), pp. 687-696.
Adaptable cooling coil performance during part loads in the tropics - A computational evaluation
Sekhar, C, Anand, P, Schiavon, S, Tham, KW, Cheong, D and Mahmoudi Saber, E. (2017). Adaptable cooling coil performance during part loads in the tropics - A computational evaluation. Energy and Buildings. 159, pp. 148-163.
A review of high temperature cooling systems in tropical buildings
Mahmoudi Saber, E., Tham, KW and Leibundgut, H (2016). A review of high temperature cooling systems in tropical buildings. Building and Environment. 96, pp. 237-249.
Ventilation effectiveness and contaminant distribution in an occupied space conditioned with low exergy ventilation technologies in the tropics
Mahmoudi Saber, E., Mast, M, Tham, KW and Leibundgut, H (2015). Ventilation effectiveness and contaminant distribution in an occupied space conditioned with low exergy ventilation technologies in the tropics. Healthy Buildings 2015 Europe. Eindhoven, Netherlands 18 - 20 May 2015 London South Bank University.
PV (photovoltaics) performance evaluation and simulation-based energy yield prediction for tropical buildings
Mahmoudi Saber, E., Lee, SE, Manthapuri, S, Yi, W and Deb, C (2014). PV (photovoltaics) performance evaluation and simulation-based energy yield prediction for tropical buildings. Energy. 71, pp. 588-595.
Numerical Modelling of an Indoor Space Conditioned with Low Exergy Cooling Technologies in the Tropics
Mahmoudi Saber, E., Mast, M, Tham, KW and Leibundgut, H (2014). Numerical Modelling of an Indoor Space Conditioned with Low Exergy Cooling Technologies in the Tropics. 13th International Conference on Indoor Air Quality and Climate. Hong Kong 07 - 12 Jul 2014 London South Bank University.
Thermal comfort and IAQ analysis of a decentralized DOAS system coupled with radiant cooling for the tropics
Mahmoudi Saber, E., Iyengar, R, Mast, M, Meggers, F, Tham, KW and Leibundgut, H (2014). Thermal comfort and IAQ analysis of a decentralized DOAS system coupled with radiant cooling for the tropics. Building and Environment. 82, pp. 361-370.