Research on the design and application of capillary heat exchangers for heat pumps in coastal areas

Journal article


Bai, Z., Li, Y., Zhang, J., Fewkes, A. and Zhong, H. (2021). Research on the design and application of capillary heat exchangers for heat pumps in coastal areas. Building Services Engineering Research and Technology. 42 (3), pp. 333-348. https://doi.org/10.1177/01436244211001497
AuthorsBai, Z., Li, Y., Zhang, J., Fewkes, A. and Zhong, H.
Abstract

This study investigated the optimal design of a capillary heat exchanger device for the heat pump system and its innovative engineering application in a building. The overall aim was to use a capillary heat exchanger to obtain energy in coastal areas for promoting renewable energy in low-carbon building design. Initially, the main factors affecting the efficiency of the capillary heat exchanger were identified, a mathematical model was then established to analyse the heat transfer process. The analysis showed the flow rate and the capillary length are the key factors affecting the efficiency of the capillary heat exchanger. Secondly, to optimize the structural design of the capillary heat exchanger, the heat energy transfer is calculated with different lengths of the capillary under various flow rates in summer and winter conditions, respectively. Thirdly, a typical building is selected to analyse the application of the capillary heat exchanger for extracting energy in the coastal area. The results show the performance of the selected capillary heat exchanger heat pump system, in winter, the heat energy transfer rate is 60 W/m2 when the seawater temperature is 3.7 °C; in summer, the heat energy transfer rate is 150 W/m2 when the seawater temperature is 24.6 °C. Finally, the above field test results were examined using a numerical simulation model, the test and simulation results agree with each other quite well. This paper is conducive in promoting the development of the capillary heat exchanger heat pump as an innovative sustainable technology for net-zero energy and low carbon buildings using renewable energy in coastal areas.
Practical application: A recently proposed capillary heat exchanger is used as an energy extraction and utilisation device to obtain energy in coastal areas for promoting renewable energy in low-carbon building design. This paper explores the application of a capillary heat exchanger as both cold and heat sources for application in typical low-rise buildings. The analysis of the heat energy transfer rate of a typical low-rise building located in a coastal area in summer and winter provides guidance for the application of capillary heat exchangers.

Year2021
JournalBuilding Services Engineering Research and Technology
Journal citation42 (3), pp. 333-348
PublisherSage
ISSN1477-0849
Digital Object Identifier (DOI)https://doi.org/10.1177/01436244211001497
Publication dates
Print10 Mar 2021
Publication process dates
Deposited26 Feb 2024
Publisher's version
License
File Access Level
Open
Permalink -

https://openresearch.lsbu.ac.uk/item/967ww

  • 10
    total views
  • 3
    total downloads
  • 1
    views this month
  • 0
    downloads this month

Export as

Related outputs

Performance evaluation of solar chimney in tunnel for passive ventilation and smoke exhaustion: A numerical approach
Huang, Y., Wang, B., Shi, L., Zhong, H. and Dong, B. (2024). Performance evaluation of solar chimney in tunnel for passive ventilation and smoke exhaustion: A numerical approach. Applied Thermal Engineering. 238, p. 122227. https://doi.org/10.1016/j.applthermaleng.2023.122227
An investigation into the efficacy of the pulse method of airtightness testing in new build and Passivhaus properties
Seddon, H. and Zhong, H. (2023). An investigation into the efficacy of the pulse method of airtightness testing in new build and Passivhaus properties. Energy and Buildings. 295, p. 113270. https://doi.org/10.1016/j.enbuild.2023.113270
Evaluating the combustion and flame extension characteristics of cable fire in utility tunnels with spontaneous combustion scenarios: An experimental study
Xu, D., Li, Y., Li, J., Zhong, H., Li, J., Tu, D. and Huang, Y. (2023). Evaluating the combustion and flame extension characteristics of cable fire in utility tunnels with spontaneous combustion scenarios: An experimental study. Tunnelling and Underground Space Technology. 140, p. 105244. https://doi.org/10.1016/j.tust.2023.105244
Enhancing solar chimney performance in urban tunnels: Investigating the impact factors through experimental and theoretical model analysis
Huang, Y., Liu, X., Shi, L., Dong, B. and Zhong, H. (2023). Enhancing solar chimney performance in urban tunnels: Investigating the impact factors through experimental and theoretical model analysis. Energy. 282, p. 128329. https://doi.org/10.1016/j.energy.2023.128329